Shared Flashcard Set

Details

Steam Pressure Control
ILT '09
19
Other
Not Applicable
03/02/2008

Additional Other Flashcards

 


 

Cards

Term
Function of pressure control system
Definition
Operate turbine control valves and bypass valves to control reactor pressure and turbine speed.
Term
Why is pressure control important?
Definition

Without pressure control, a rise in turbine demand, would open the control valves, which would drop pressure, reducing reactor power which would open the control valves further…

 

In other words, the pressure control system provides a necessary feedback mechanism.

Term
Range of mechanical pressure regulator
Definition
per B-manual, 120 psig to 1050 psig
Term
Range of electrical pressure regulator
Definition
900 psig to 1000 psig
Term
When is mechanical pressure regulator used?
Definition
Due to its wide range, it is used during startup and shutdown. It is also used as a backup to the electrical pressure regulator (setpoint set higher).
Term
Location and power supply to Electrical Pressure Regulator
Definition
Location: Cable Spreading room; Power supply: Y-30
Term
Where can Pressure Regulator Override be operated?
Definition
Panel C-07 or locally (front standard)
Term
Discuss operation of the Pressure Regulator Override
Definition
Can be used to manually open the control and bypass valves. May be used to vent the reactor and to establish steam flow through the bypass valves during startup provided the control valves are held shut by load limit or speed/load changer. If not, the PRO will fully open control valves first.
Term
Discuss the flow limit control
Definition
Mechanical stop in the control linkage system to limit the maximum opening of the control and bypass valves. Adjusted so that the total steam flow is restricted to slightly greater than reactor rated flow.
Term
Describe the indicating lights on C-07 that show which of the three inputs (MPR, EPR, PRO) is controlling.
Definition
Red light: controlling; Green light: Not controlling. It is possible to have two red lights).
Term
Purpose of the speed governor
Definition

Acts on the error signal between turbine speed and the speed setpoint (as determined by the position of the speed/load changer) and positions the control valves to maintain proper turbine speed.

 

NOTE: turbine speed is fixed at 1800 RPM when on the grid.

Term
Function of Speed/Load Changer
Definition

Used for synchronizing the generator during startup and for turbine load demand once the generator is tied to the grid.

 

Will not control below 95%.

Term
Function of Load Limit
Definition
Limit the load on the turbine to any desired level. Normally used to open the control valves during startup until Speed/Load changer assumes control. Latched by turbine trip oil so if turbine trips, control valves automatically close.
Term
What is the typical difference between EPR and MPR setpoint?
Definition
No less than 10 psi and no greater than 18 psi.
Term
When is a shutdown of EPR allowed?
Definition
All pressure regulators are required unless reactor power is less than 25% or between 90 and 100%.
Term
Discuss an EPR failure upscale
Definition
EPR input to HVG1 will be negative which means that MPR will control.
Term
Discuss an EPR failure downscale
Definition
EPR will remain in control and control valves and bypass valves will open. Eventually scram will occur (after Group I isolation… 840 psig in run).
Term
Summarize the MPR/EPR failures
Definition
A failure causing one steam pressure signal to go up will result in other regulator controlling. A failure causing the steam pressure signal to drop will result in a high signal with no backup from the other regulator. Control valves will fully open, bypass valves will open. Group I isolation at 840 psig (in run) and automatic reactor scram (MSIV closure).
Term
Per the C.4 for Loss of Pressure Control Resulting in a Drop in Steam Pressure, above what pressure difference between EPR and MPR would an automatic reactor scram occur upon securing the EPR?
Definition

Pushing the EPR STOP pushbutton on C-07 with MPR available will remove the EPR from service and Reactor pressure should increase to the MPR setpoint. If this action is taken when the difference between Main Steamline pressure

and MPR setpoint is greater than approximately 15 psi, the resulting pressure transient will

most likely result in an automatic Reactor Scram (on high neutron flux).

Supporting users have an ad free experience!