Shared Flashcard Set

Details

Core Spray
ILT '09
30
Other
Not Applicable
01/26/2008

Additional Other Flashcards

 


 

Cards

Term
Describe the Core Spray Inboard/Outboard Isolation Valve Interlock
Definition
Neither valve may be opened if the other is not fully closed; bypassed for inboard valve ONLY when reactor pressure is less than 420 psig. The interlock forces the operator to open the outboard isolation valve first when performing a manual initiation of the system.
Term
How can core spray be isolated with an initiation signal present?
Definition

Keylocked bypass switch on Panel C-03 allows operation of the OUTBOARD isolation valve.

 

Also, INBOARD isolation valve may be operated (throttle valve)

 

NOTE: the pump switch should also be placed in "pull-to-lock.

 

 

Term
Power supply to Div I motor operated valves
Definition
MCC 133
Term
Power supply to Div II motor operated valves
Definition
MCC 143
Term
Control Power to Core spray motor operated valves
Definition
MCC 133/143
Term
Describe the connection between Core spray and Auto Depressurization Logic
Definition
Core spray provides relay contacts for Reactor Low Low Water Level in ADS logic. In addition, Core Spray provides one of the permissives for an initiation of ADS; by means of a 100 psig signal, indicating the core spray pump is running.
Term
Describe the connection between Core Spray and EDG logic
Definition
Core spray logic provides a start signal for the EDGs with a one of two taken twice logic on Reactor Low Low Water Level or High Drywell Pressure.
Term
Describe the connection between Core Spray and High Pressure Coolant Injection logic
Definition
Core Spray provides relay contacts in the HPCI start logic for High Drywell Pressure.
Term
Describe the connection between Core Spray and Reactor Core Isolation Cooling logic
Definition
Core spray provides relay contacts for Reactor Low Low Water Level in the RCIC initiation logic.
Term
What does the condensate service system do for core spray?
Definition
Keep fill of at least 30 psig (normally 40 psig) which minimizes the chance of water hammer.
Term
Besides logic, what is another connection between core spray and HPCI?
Definition
The HPCI min flow line ties into B loop Core Spray test return line.
Term
Besides logic, what is another connection between core spray and RCIC?
Definition
The RCIC minimum flow line ties into A loop core spray test return line.
Term
Function of Core spray
Definition
Restore and maintain reactor coolant during a loss of coolant accident in combination with other emergency cooling systems.
Term
Core spray rated flow (and associated reactor pressure)
Definition
3020 gpm when reactor pressure has dropped to 145 psig.
Term
Purpose of core spray orificed min flow line.
Definition
Designed to allow a flow of 300 gpm at pump shutoff head to prevent pump damage after an automatic start until the isolation valves are opened and flow to the vessel is initiated.
Term
Purpose of Core spray relief valve
Definition
Set at 500 psig to protect the piping between the pump and testable check valve from over-pressurization when both isolation valves are open.
Term
Discuss the sequence of events that occur upon receipt of an automatic initiation of Core spray.
Definition
In each loop: Core spray pump starts after a 15 second time delay. Core Spray test return line valves isolate. When reactor pressure reaches 420 psig, inboard and outboard isolation valves automatically receive an open signal. Due to the discharge head of the pump (375 psig) and head losses, flow does not commence until reactor pressure reaches approximately 310 psig.
Term
High drywell pressure
Definition
1.84 psig
Term
Reactor Low Low level
Definition
-47 inches indicated
Term
Low reactor pressure
Definition
420 psig
Term
Conditions required for auto initiation of core spray
Definition
  • High drywell pressure (1.84 psig) one-of-two taken twice
  • Reactor low low water level (-47 inches) one of two taken twice AND
    • Reactor pressure less than 420 psig, one of two OR
    • Reactor low low water level for 20 minutes one out of two
Term
Explain core spray leak detection.
Definition
Differential pressure sensed between above the core plate (HP) and the Core spray discharge line downstream of the testable check valve (LP). If discharge line is intact, pressure sensed will be inside core shroud. If there is a break in the piping between the vessel wall and shroud, the pressure sensed will be the downcomer region. NOTE: Due to relative densities, the differential pressure is negative. With a break in the discharge line, the differential pressure will be LESS NEGATIVE.
Term
Discuss RHR room heatup analysis and consequences
Definition
Analysis assumes coolers are started within 13 minutes of accident initiation when all three pumps are running. Therefore, if room coolers are unavailable, RHR and Core spray pumps in that room are INOP.
Term
What is a consequence of not having ECCS sump pumps?
Definition
Associated RHR and Core spray pumps are considered inoperable.
Term
Core spray minimum indicated flow restrictions
Definition

Continuous operation: 2000 gpm

 

Short-term operation (less than 2 hours in 24 hours): 1500 gpm.

 

NOTE: minimize time spent operating with indicated flow less than 2000 gpm.

Term
Non-emergency core spray motor start restrictions
Definition
Two starts in succession from ambient temperature or one start from rated temperature. For subsequent starts, allow thirty minutes running time at full speed or sixty minutes idle time.
Term
Discuss the dual safety function of the core spray valves
Definition
Valves must operate in the OPEN direction for the Core Spray System to be operable. And must operate in the CLOSE direction for the Primary containment system to be operable.
Term
Concerns with closing the Outboard Core spray isolation valve
Definition
Pressure locking. Therefore ANY time the outboard isolation valve is closed, the "associated subsystem" is considered inoperable.
Term
Concerns with opening test return valves
Definition

MO-1749 does not close on torque and therefore may not prevent diversion of flow upon receipt of an auto intiation signal.

 

Although MO-1750 logic was recently changed to close on torque, it is still lumped into the above category. Hence, if either test return valve is open, the associated subsystem is considered inoperable. No longer the case as of Feb. 2008

Term
ECCS Design Criteria
Definition
  • Peak Cladding Temperature < 2200 degrees F
  • Max local cladding oxidation < 17% of the total thickness before oxidation
  • < 1% Hydrogen generation
  • Coolable geometry
  • Long term cooling
Supporting users have an ad free experience!