| Term 
 
        | Excore Nuclear Instrumentation System Purpose: |  | Definition 
 
        |  Protect the reactor by monitoring neutron flux and generating reactor trip input signals to the Reactor Protection System (RPS) during various operational conditions. 
Indication and recording of:  Reactor Power  Power Distribution  Rate of Change of Reactor Power  During startup, shutdown, power and refueling operations. 
Supplies signals relating to power distribution to RPS Over-temperature Delta-T (OT∆T) and Overpower Delta-T (OP∆T).  Supplies signals relating to nuclear power to Rod Control System.  Generates signals to actuate annunciators when:  Setpoints are reached  Equipment failures occur  Channels are in test  Gamma-Metrics provides independent, qualified, neutron flux measurement (full range).      |  | 
        |  | 
        
        | Term 
 
        | Excore NIs Design Basis: Source Range-Safety Related |  | Definition 
 
        |   
Provide indication and protection against Boron Dilution accident at low power.  Provide core protection against a Rod Withdrawal accident.  Provide indication of Reactivity Changes that may occur.    |  | 
        |  | 
        
        | Term 
 
        | Excore NIs Design Basis: Intermediate Range-Safety Related |  | Definition 
 
        | Protection against reactivity excursions from an inadvertent Boron Dilution accident. 
From sub critical or low power conditions, protect against reactivity excursions from an Uncontrolled RCCA Withdrawal. Protect against reactivity excursions from an RCCA ejection.  Input to P-6  
1/2 IR detectors 1x10-10 Amps Allows block of SR Hi Flux Rx Trip and SR high voltage de-energization2/2 IR detectors 7x10-11 Amps Energizes SR Hi Volts and unblocks SR Hi Flux Rx Trip   |  | 
        |  | 
        
        | Term 
 
        | Excore NIs Design Basis: Power Range- Safety Related |  | Definition 
 
        | Provide high flux trips that protect against reactivity excursions caused by: 
Inadvertent Boron Dilution accident.  An Uncontrolled RCCA Withdrawal accident.  RCCA ejection accident  Feedwater malfunction (loss of FW heating)  Provide Positive Rate Trip  Protects against RCCA ejection of low worth rods at mid power. 
Provide input to the OP∆T and OT∆T protection circuits  Provide input to the protection permissives:  P-7 (via P-10) P-8 
Provide input to the protection permissives:  §P-9 (Turbine Trip / Rx Trip coincidence)  • §P-10  •
   |  | 
        |  | 
        
        | Term 
 
        | Excore NIs Design Basis: Source, Intermediate and Power Range- NSR |  | Definition 
 
        | Source Range Nuclear Instruments 
Visual display of count rate  Visual display of startup rate  Audible count rate signals 
Intermediate Range Nuclear Instruments  
Visual display of detector current  Visual display of startup rate  
Input to C-1, High Flux Rod Withdrawal Stop 
Power Range Nuclear Instruments  Visual display of reactor power  Visual display of axial flux difference  Input to C-2, High Flux Rod Withdrawal Stop  Input to C-3, OP∆T Rod Withdrawal Stop  Input to C-4, OT∆T Rod Withdrawal Stop  Input to Rod Control Power Mismatch circuits  Input to NIS detector and channel comparator alarms      |  | 
        |  | 
        
        | Term 
 
        | Source Range Detectors N31 and N32 Location, Type and Power Supply |  | Definition 
 
        | Located in detector wells on opposite sides of the core at 0o  and 180o ; core centerline and approximately ¼ core height, ensures detector is located in area of maximum flux during reactor startup Detector wells are shared with the intermediate range detectors (N35, N36) Type  Boron Trifluoride (BF3) gas filled proportional counters 
§BF3 because 5B10 will allow 0n1 detection   §Proportional range highly sensitive at low flux levels 
§Packed in polyethelyne to slow down fast neutrons to thermal energies before they enter the detector Power 
N31, A SR Drawer is powered from “A” 115 VAC VIB  N32, A SR Drawer is powered from “B” 115 VAC VIB  High voltage power supply produces ~ + 2100 VDC for operation of the BF3 proportional detector.            If voltage to the detector drops > 100 VDC from its nominal value a control room overhead alarm will alert the operator.  (SR DET VOLT TRBL, OHA E-5) |  | 
        |  | 
        
        | Term 
 
        | Excore NIs: SR Components Pre-Amp |  | Definition 
 
        | Without a preamplifier the long cable length and very low signal strength would result in signal loss. 
§Preamp keeps the signal to noise ratio as high as possible    |  | 
        |  | 
        
        | Term 
 
        | Excore NIs SR Components: Pulse Amp Discriminator |  | Definition 
 
        | 
Three functions of Pulse Amplifier / Discriminator:  §Amplify signal output from preamplifier  §Eliminate unwanted noise and gamma pulses  §Permit testing of circuitry  Output signal is sent to:  §Pulse Shaper  §Audio Count Rate channel through an isolation amplifier      |  | 
        |  | 
        
        | Term 
 
        | Excore NIs Components- Isolation Amplifier  
 |  | Definition 
 
        | Isolate the non-safety related outputs from the safety related circuitry 
 
§Ensures that a failure in the non-safety related portion does not affect the rest of the circuitry from performing safety related functions.    |  | 
        |  | 
        
        | Term 
 
        | Excore NIs SR Components: Pulse Shaper |  | Definition 
 
        | Produces one amplified square wave for every two pulses |  | 
        |  | 
        
        | Term 
 
        | Excore NIs SR Components: Pulse Driver |  | Definition 
 
        | Impedance matches HRT pulse shaper output HRT to the log pulse integrator |  | 
        |  | 
        
        | Term 
 
        | Excore NIs SR Components:  Log Pulse Integrator   |  | Definition 
 
        | Provides DC output current proportional to the input pulse |  | 
        |  | 
        
        | Term 
 
        | Excore NIs SR Components: Level Amp |  | Definition 
 
        | Amplifies Log Pulse Integrator Output   Test Signal (0 to 106 cps, variable)   Feeds: 
Isolation Amplifier with all NSR loadsBistable- SR Hi Flux S/DBistable- 1/2 >105  cps Rx TripLocal Indication  
   |  | 
        |  | 
        
        | Term 
 
        | Gas Filled Detector Six Regions Region, Description and Location |  | Definition 
 
        | I Recombination Region: ion pairs recombine before reaching detector anode (Inner chamber of IR detector) II Ionization Region: all ion pairs reach detector anode (outer chamber of IR detector; PR detector) III Proportional Region: motion of ions causes additional ionization of the gas, proportional to the ionizing event (SR detector) IV Limited Proportional Region: Motion of the ions causes additional ionization of the gas, NOT proportional to the ionization event (none) V Geiger-Mueller Region: Single Ionization event causes all the gas molecules to ionize (GM "frisker" detector) VI Continuous Discharge Region: Continuous discharge between anode and cathode, regardless of ionizing events (none) |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | 
E-13 SR High Flux at S/D- SR indication > 0.5 decade above bkgrndE-5 SR Det Volt Trbl- SR volts <100 VDC below normalE-21 SR High Flux at S/D Blocked- High Flux at S/D switch Block positionE-29 SR and IR Trip Bypassed-SR or IR Level Trip switch in Bypass positionA-5 NIS Channel in Test- SR operation selector switch not in normal positionF-25 SR High Flux Rx Trip- SR Indications >106  cps with level trip switch in normal and/or Hi Level Trip unblocked |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | 
Manual Block of Hi Flux Trip enabled wjen 1/2 IR channels above P6(1x10-10Amps)SR Detector auto deenergized when 2/4 PR Channels above P10 (10% Power)SR Detectors manual unblock enabled when 3/4 channels below P10 (10% power)Hi Flux Trip unblocked and SR detectors auto energized when 2/2 IR channels below P6 (7x10-11Amps) |  | 
        |  | 
        
        | Term 
 
        | SR Instruments- Impacts of Rx Power vs Instrument Failures-Table |  | Definition 
 
        | Rx Pwr:         Below P6     >P6 (not Blocked)   >P6 and Block or >P10 
 Lvl Trip Sw:  Norm/Bypass       Norm/Bypass         Norm/Bypass 
 Loss Instr    Rx Trip/No Trip       Rx Trip/No Trip      NoTrip/No Trip Power: 
 Loss Cntrl    Rx Trip/Rx Trip      Rx Trip/Rx Trip       NoTrip/No Trip Power: |  | 
        |  | 
        
        | Term 
 
        | Excore NIs IR Detectors N35 and N36: Location, Type, Power Supply |  | Definition 
 
        | Located in detector wells on opposite sides of the core at 0o  and 180o ; core centerline and approximately ¼ core height, ensures detector is located in area of maximum flux during reactor startup Detector wells are shared with the isource range detectors (N31, N32) Type Compensate Ion Chambers (CIC) 
§wrapped in polyethylene sleeves to slow down fast neutrons §CIC consists of 2 concentric cans   
Power 
N35, A IR Drawer is powered from “A” 115 VAC VIB N36, A IR Drawer is powered from “B” 115 VAC VIB 
CIC High Voltage Power Supply  CIC high voltage power supply produces +300 to +1500 VDC  Low voltage condition actuates OHA E-6 at 100VDC below nominal  CIC Compensating Voltage Power Supply  Generates a negative potential up to –100VDC  Low voltage condition (~50% of nominal) actuates OHAs E-14 (N35), E-22 (N36)    |  | 
        |  | 
        
        | Term 
 
        | Excore NIs IR Overcompensated vs Under Compensated |  | Definition 
 
        | Over Compensated: Occurs when the Compensation voltage is too high. This causes the indicated value to be lower than actual neutron population. On S/D, may cause the IR current to decrease below the P6 setpoint earlier than normal. If both IRs set wrong, would cause the SR detectors to energize at a higher than normal flux level. On S/U if both iRs set wrong, could cause High SR Trip before recieving permissive to block the SR trip. Also results in false high, SUR indication.  
 Under Compensated: Occurs when the Compensation voltage is too low. This causes the indicated value to show higher than actual neutron population. On S/D may cause the IR current to stay above the P6 setpoint, preventing the SR detectors and HVPS from automatically energizing. SRs can be manually unblocked. On S/U could allow block of SR trip early. Indicated SUR will be less than actual SUR. 
 At 10-11 amps, curve flattens out due to circuit "live zero" when set properly, IR is set slightly undercompensated. |  | 
        |  | 
        
        | Term 
 
        | Excore NIs IR Components: IR Det Volt Loss and IR Compensating Volt Loss Bistables |  | Definition 
 
        | Both Fed from CIC IR DET Volt Loss will generate alarm if the detector volts see more than 100 volt loss.   IR Compensating Volt Loss will generate an OHA if the detector see <50% of normal voltage (E-14 and E-22) |  | 
        |  | 
        
        | Term 
 
        | Excore NIs IR Components:   Log Current Amp |  | Definition 
 
        | Provides amplified output proportional to the logarithum of the input. (Fed by Operation Selection Inputs and Amp Idling  Current (live zero) which prevents 0 input to amp during absence of detector output.   Feeds the following:   
Isolation Amplifier- NSR loads10-10Amps Bistable (P6 SR Block Permissive)Current = 25% Power to Level Trip Bypass and IR High Flux Rx TripCurrent =20% Power to Level Trip Bypass and IR High Flux Rod Stop               |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | 
E-30, IR High Flux Rod WDRWL Stop, IR indication >20% power and IR Trip UnblockedE-6, IR Det Volt Loss, IR 100 volts below normal voltage setpointE-14, IR N35 Compensating Volt Loss, Compensation Voltage <10% normal voltage (-100VDC)E-22 IR N36 Compensating Volt Loss, Compensation Voltage <10% normal voltage (-100VDC)A-5, NIS Channel in test, IR operation selector switch is not in normal positionF-17 IR Flux Hi, > 25% power and IR High Flux TripE-29 SR & IR Trip Bypassed, IR level Trip Bypass switch in Bypass Position |  | 
        |  | 
        
        | Term 
 
        | IR Detectors: Impacts of RX Power vs Instrument Failures-Table |  | Definition 
 
        | Rx Pwr:         Below P10     >P10 (not Blocked)   >P10 (Blocked)* 
 Lvl Trip Sw:  Norm/Bypass       Norm/Bypass         Norm/Bypass 
 Loss Instr    Rx Trip/No Trip       Rx Trip/No Trip      NoTrip/No Trip Power: 
 Loss Cntrl    Rx Trip/Rx Trip      Rx Trip/Rx Trip       NoTrip/No Trip Power: 
 * If >P10 and IR trip is blocked- SSPS internal circuitry inhibits the IR High Flux Trip and Rx IR Rod Stop, independent of status of IR drawer 120 VAC Instrument and Control Power. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | The IR instrumentation is required in Mode 1 (<P10) and Mode 2 
 One IR Channel INOP- 
Mode 1 (<P10) and 2(>P6) Restore to Operable prior to increasing power >10% (NOTE: TS 3.04 is applicable, so if power is >5%, do not increase power above 5%Mode 2 (<P6) Restore to operable prior to increasing power above P6 setpoint. Two IR Channels INOP- 
Mode 1 (<P10) and 2, enter TS 3.03Mode 1 (>P10) The provisions of TS 3.03 are not applicable. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | The SR instruments are require in Mode 2 (<P6, with Rx Trip System Brkrs in Closed Position and CRD system capable of rod withdrawl) through Mode 6. In mode 6 each SR must have continuous visual indication, in the MRC and one must have audible indication is the containment and MCR.   1 SR Channel INOP 
Above P6- observation may continueMode 2 <P6, Restor inop channel to Operable prior to increasing thermal power above P6Mode 6 Immediately suspend core alternations or positive reactivity changes 2 SR Channel INOP  
Mode 3-5 Verify SDM within 1 hour and once per 12 hrs thereafterMode 6, Immediately suspend core alterations or positive reactivity changes and determine RCS B- conc. at least once per 12 hrs thereafter (TS 3.03 is NOT APPLICABLE) |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | The PR instruments are required in Mode 1 and 2 (The High Flux Low Set Point Trip is required in Mode 1 below P10, and Mode 2) The provisions of TS 3.04 do not apply to PR instrumentation.   1 PR Instrument INOP 
Place INOP Channel in tripped condition within 6 hrsPerform QPTR every 12 hrs or reduce power <75% and PR Trip setpoints to <85% within 4 hrs (inoperable Channel can be bypassed for upto 4 hours for testing of other channel) 2 PR Instruments INOP  |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR  Location, Type and Power Supply |  | Definition 
 
        | Location: Surround the RX at 45, 135, 225 and 315°, upper and lower detector at each location.   Type:  
Uncompensated Ion Chambers (UIC)  §Gamma Flux is Proportional to Neutron Flux - Both are proportional to Power  §Neutron Flux is much greater than Gamma Flux – Gamma Flux is insignificant  Nitrogen filled with boron lining.  
NOT wrapped in polyethylene, b/c ample thermal neutron leakage    
Advantages of 2 detectors: Smaller detectors are easier to manufacture and install  Allows monitoring of power being produced in top and bottom half of the core independently. (Axial Flux Difference)   Power Supply: Powered from A-D 115 VIB |  | 
        |  | 
        
        | Term 
 
        | Excore NIs- PR Quadrant Power Tit Ratio (QPTR) |  | Definition 
 
        | QPTR is defined as the ration of the maximum upper excore detector calibrated output to the average of the upper excore detector calibrated output or the ratio of the maximum lower excore detector calibrated output, whichever is greater. The upper and lower current comparators perform  the same function as the process computer in calculating QPTR. If a 2% or greater deviation exists (QPTR > 1.02) then the upper or lower current comparator will generate an alarm to indicate QPTR > 1.02. |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR- Permissives Table |  | Definition 
 
        | P6 SR Permissive: Initiates: 1/2 IR Channels > 10-10 amps Resets: 2/2 IR Channels <7 x 10-11 amps Function: Allows Manual Block of SR High Flux Trip Automatically re-energizes SR detectors when reset P10 At Power Permissive: Initiates: 2/4 PR Channels > 10% Power Resets: 3/4 PR Channels<10% Function:  De-energize SR High Voltage Blocks SR High Flux Trip Inputs to P7 Allows Manual Block of IR High Flux Trip Allows Manual Block of PR (Low Set point) High Flux Trip 
 P7 Low Power Permissive: Initiates:1/2 Inputs P10 and P13 Resets: Both P10 and P13 clear Function: Unblocks 6 Rx Trips when above P-7 2/4 RCS Low Flow RCP Bus Underfrequency RCp Bus Undervoltage Pzr Low Pressure Pzr High Level 2/4 RCP Breakers Open 
 P-8 Low Flow: Initates: 2/4 PR Channels > 36% power Resets3/4 PR Channels <36% Function: When >P-8, 1/.4 RCS Low Flow When <P8 and > P7, 2/4 RCS Lower P-9 Initates: 2/4 PR Channels>49% power Resets: 3/4 PR Channels < 49% Function: When above P9, Enables auto Rx Trip when we have a turbine trip When below P-9, Disables turbine trip. 
  
  
 |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | 
E-15, PR Hi RNG Flux High, 1/4 PR channels > 109%E-38, Upper Sect Dev. ABV 50% Pwr, Upper Detector deviation ratio of 1.02 with any channel > 50%E-23, PR Lo RNG Flux Hi, 1/4 PR Channels > 25% with PR low Set Point Rx trip not blockedE-46, Lower Sect Dev. ABV 50% Pwr, Lower Detector deviation ratio of 1.02 with any channel > 50%E-31, PR Overpwr Rod Stop, 1/4 PR Channels > 103%E-47, PR Neut Flux Rate Hi, 1/4 PR channels change +/- 5% with 2 sec time constantE-39, PR Channel Deviation, 4% difference between highest and lowest PR Channel outputsE-7, PR Det Volt Loss, PR 100 volts below normal voltage set pointA-5, NIS Channel in Test, PR operation selctor switch not in Normal positionF-1, PR Hi Rng Flux Hi, 2/4 PR channels > 109%F-9, PR Lo Rng Flux Hi, 2/4 PR Channels > 25% with PR low setpoint Rx Trip not blockedF-33, PR Flux Rate High, 2/4 PR Channels change +/- 5% with 2 sec time constant |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components- Channel and Rate Drawer |  | Definition 
 
        | Powered from D 115 VAC VIB Loss of Power disables to the Comparator Channel Defeat switch and will not function Indications: 
-5 to 5 decade Meter- Indicates the SUR of this channel selected via the Channel selector switch.Channel Deviation Light- Lit when a 4% deviation exists between the highest and lowest of all 4 PR channel output levels (OHA E-39)Comparator Defeat-lit when Comparator Channel Defeat Switch is not in Normal PositionInstrument and Control Power Lights- Lit when power is available.Rate Channel Test- Lit when Rate Test switch is not in normal positionComparator Channel Defeat Knob- Takes PR channel out of the comparator circuitry (4% difference between channels)SUR-Channel Selector Knob- Selects a channel to indicate SURSUR Rate Test Knob- Inserts a 1.0 or 5.0 dpm test signal to the meter   |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components Detector Current Comparator Drawer |  | Definition 
 
        | Powered from D 115 VAC VIB. Loss of Power disables the Upper and Lower Section defeat switches. The Rod Stop Bypass and Powere Mismatch Bypass switches are unaffected by a loss of power and are still functional. 
 Indications: 
All Channels below 50% FP- Lit when all 4 PR upper detector currents are below 50% of the 100% current value for that detectorChannel Defeat- Lit when upper section defeat switch is not in normal positionUpper Selection Deviation- Lit when 1 detector current in upper plane of the core reads 1.02 different from the average of the 4 detector currents in the same plane (QPTR) OHA E-38All Channels below 50% FP- Lit when all 4 PR lower detector currents are below 50% of the 100% current value for that detectorChannel Defeat- Lit when lower section defeat switch is not in normal positionUpper Selection Deviation- Lit when 1 detector current in lower plane of the core reads 1.02 different from the average of the 4 detector currents in the same plane (QPTR) OHA E-46Section Knobs (Upper/Lower)- defeats an upper section detector current input to the comparator circuitryRod Stop Bypass (N41/N43 and N42/N44)- Removes the selected channel from the Rod Stop (C-2) circuitry (RP4 Blue Light)Power Mismatch Bypass- Removes the selected channel from the Rod Control System input |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components: Power Range A Drawer |  | Definition 
 
        | Loss of either control or instrument power to PR drawers will result in tripping all bystables in the associated drawer. 
 Indications: 
Fuses- Lit when the instrument power is lost, all lights are dark when control power is lost.Control Power On- Lit regardless of power level unless control power is lostLoss of Dector Voltage- Lit when detector voltage 100 volts below normal.Overpower Trip High Range- Lit with Channel above 100%Overpower Rod Stop-Lit with Channel above 102% (C-2)Overpower Trip Low Range- Lit with channel above 25%Power Above Permissive P10- Lit with Channel above 10%,P-10Power Above Permissive P-6- Lit with Channel above 36%, P-6Positive Rate Trip- Indicates channel level rises >5% with 2 sec time constantNegative Rate Trip- indicates channel level lower >5% with 2 sec time constantPower Above P9- Lit with Channel above 49%, P9Rate Mode Knob- resets + and - rate trip |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components Power Range B Drawer |  | Definition 
 
        | Loss of either control or instrument power to PR drawers will result in tripping all bystables in the associated drawer. 
 Indications: 
Amp Meters- indicate actual detector current (unnormalized)Operation Selector-Allows testing of either or both detectorsOperation Selector-Gain- adjusts the level of the drawer output not the level of the detector current (normally adjusted during Calometric BOS)Detector A/B Test signal- Inserts variable test signal whent he operation selector switch is selected to the specific detectorRange Milliamps Knob- ranges detector current meter.Instrument power on- lit regardless of power level, unless power is lostChannel On Test- lit when operation selector switch is not in normal. |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components: Circuitry Detector Outputs |  | Definition 
 
        | Upper and Lower Detector share PR Det Volt Loss Bystable, which monitors the high voltage supply (100 VDC below normal, OHA E-7) 
Each detector feeds its own Detector CurrentEach detector feeds its own Isolation Amplifier for Δi to OTΔT and OPΔT CircuitsEach detector feeds its own Isolation Amplifier for NR-45, Upper (lower) detector current recorder, P-250, Percent Δi meter. Upper (lower) current comparator defeat switch, Comparator and OHAs E-38 Upper Detector Deviation High (>2% Difference from avg of four) or E-46 Lower Detector Deviation High (>2% Difference from avg of four) Both detectors feed the Summing and Level Amp Gain Pot. |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components Circuitry Detector Outputs-Bistables |  | Definition 
 
        | 
Low Range Hi Flux (25%)-OHA E-23 (1/4) OR Rx Trip (2/4)P10, PR and IR High Flux Trip Block (10%)-(2/4)High Range Hi Flux Trip(109%)- OHA E-15 (1/4) OR Rx Trip (2/4)High Range Hi Flux Rod Stop C-2 (103%)- OHA E-31 (1/4) OR Rod Stop (1/4), has the Rod Stop Bypass SwitchP8, 3 Loop Flow (36%)P9, Turb/Rx Trip (49%) Rate Comparator Feeds 2 Bistables and Local Indication 
Local Indications (0-120% Local indication)High Positive Flux Rate (+-5% sec TC)-OHA E-47 (1/4) OR  Rx Trip (2/4)High Negative Flux Rate (+-5% sec TC)-OHA E-47 (1/4) OR  Rx Trip (2/4) 
 
 |  | 
        |  | 
        
        | Term 
 
        | Excore NIs PR Components CircuitryDetector Outputs- Isolation Amplifiers fed from Summing and Level Amp Gain Pot |  | Definition 
 
        | Isol Amp-> Power Mismatch Bypass Switch-> feeds and auctioneered high circuit (compares 4 PR instruments) and sends signal to Rod Control (Power Mismatch) and AFD.  
 Isol Amp-> MCB Meter, NR45, Plant Process Computer, SPDS 
 Isol Amp-> Channel Comparator Defeat Switch -> Comparator (looks at all 4 PR instruments) and will initiate OHA E-39 Channel Deviation Alarm when >5% Difference between two channels This Isol Amp also feeds the Overpower Recorder (0% to 200%) |  | 
        |  |