        | Provide reliable cooling for potentially Rad Safety and NSR loads during all operational modes and a DBA. Closed loop system provides an additional barrier  to prevent direct release of radioactivity to Delaware River. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | 
Transfer heat from SR/NSR loads to SW during normal operations and DBAs. CCW pressure is < SW pressure. CCW design pressure is 150 psig @ 200 F, except in Containment- RCP thermal barrier 650F and 2485 psig.ESF System: 2 independent parallel trains consisting of one Pp and one HX. Each train Powered by Class 1E and Diesel. Each train capable of bringing the plant to cold Shutdown following postulated LOCA, Concurrent with LOP and DBA earthquakeSized such that SW at 90F, will make CCW <99F at all times.Provided with Design features to detect leakageRCP thermal barrier Leak detection isolationCCW Surge Tank relief valve can hold postulate RCP thermal Barrier leak to CCWRelief valves provided to CCW HX to prevent overpressurization due to thermal expansionContainment Auto isolation ValvesDesigned for Shutdown Concurrent with MCR evacuation (operation from HSD Panels) |  | 
        |  | 
        
        | Term 
 
        | CCW Surge Tank:   Purpose and Specs |  | Definition 
 
        | Provides NPSH to CCW Pps, Accommodates volume of RCS entering the CCW for 3.5 minutes following a RCP thermal barrier rupture, Accommodates System Surges and Provides means for chemical mixing. 
2000 gallons max, normal 50% full, 2 level detectorsInternal Baffle at 37.5%Make Up Water provided by DR (via DR107) or alternate source-PWST, fill valves are CC145/146Vented to Aux Bldg Exhaust Filter Inlet Header via CC149, CC149 auto closes on RMS 17 a/b high rad or failed monitor alarmTank Relief Valve CC147, set point 100 psig, passes > 285 gpm to  contaminated floor drains and then WHUT. |  | 
        |  | 
        
        | Term 
 
        | CCW Pps:   Purpose and Specs |  | Definition 
 
        | Circulate hot CCE thru CCW HX, cooled by SW. The cooled CCW is then supplied to all heat loads. 3 pps- 
21 in 21 HX Room powered by A 4 KV VB,22/23 in 22 HX Room powered by B and C 4 KV VB respectivelyCentrifugal PP max- 4600 gpm @ 200 psig, min 1100 gpm Suction Header relief valve CC138, setpoint 150 psig Normal Operation is two Pps running and one in auto standby. Auto Starts: Low Header Pressure, <70psig SEC Mode 2 blackout auto sequencer   Auto Trips: Vital Bus Overload Vital Bus Diff SEC Trip Signal Mtr Overcurrent   SEC: Mode I, if in auto will remain in auto   Mode II, III, IV take to manual and Pp will restart as needed. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | Modes 4,5,6 transfers heat from RHR HX to SW. Normal Ops (Modes 1,2,3) transfers heat from NSR loads, Accident cool RHR HX and seal coolers of SR Pps. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | 
RHR HXRHR Mechanical Seal HXSI PP Mechanical Seal HXCharging Pp (23) lube oil cooler/speed changer |  | 
        |  | 
        
        | Term 
 
        | CCW Non-Safety Related Loads |  | Definition 
 
        | 
SFP Cooling HXLTDN HXSeal Water HXWaste Gas CompressorExcess LTDN HXSample System HXPass RacksSGBD RMSRCPs- Upper Motor Cooler/ Lower Motor Cooler/ Thermal Barrier HX |  | 
        |  | 
        
        | Term 
 
        | CCW Sources of Inleakage: |  | Definition 
 
        | System Pressure is greater than CCW pressure 
RCP Thermal BarrierExcess LTDN HXLTDN HXRHR HXMechanical Seals of Running Pps   |  | 
        |  | 
        
        | Term 
 
        | CC149 CC Surge Tank Vent Valve Interlocks |  | Definition 
 
        | Auto Close on Hi Rad from R17A/B or RMS failure   Close on Loss of Control Air and   Loss of Power (28/125 V DC) |  | 
        |  | 
        
        | Term 
 
        | CC-131 RCP Thermal Barrier Discharge Flow Interlocks |  | Definition 
 
        | Containment Isolation Vlv   Auto Close if flow is > 175gpm for > 4 seconds (for leak isolation, normal flow is 160 gpm), this will mannually override the auto functions of this valve.   |  | 
        |  | 
        
        | Term 
 
        | CC215 and CC113 Excess LTDN HX Interlocks |  | Definition 
 
        | CC215(inlet to HX), CC113 (Outlet from HX)    Auto Close on:  Loss of Air Loss of 28/125V DC Containment Phase A |  | 
        |  | 
        
        | Term 
 
        | CC71 LTDN HX Temperature Control Interlocks |  | Definition 
 
        | Safety Related  AOV "Auto" maintains 100F CVCS LTDN "Manual" adjust temperature by pressing increase/decrease bezels in MRC CV7 closes and CC71 will close (CV7 closed limit swithch de-energizes the CC71 solenoid) |  | 
        |  | 
        
        | Term 
 
        | SEC Mode Responses for the CCW System: |  | Definition 
 
        | Mode I: Pps in auto and manual will be blocked until reset by SEC. What you have is what you get. After Reset, the third pp may come on as needed.   Mode II: All pps stopped and restarted in required sequence   Mode III: All pps stopped, SW122 closed and PPs do not restart.   Mode IV: Trip CCW Pp, affected SW122 closes and pps shift from auto to manual operation. Pps do not auto restart. |  | 
        |  |