| Term 
 
        | HVAC 
 Describe fans with heating coils trip setpoint.
 |  | Definition 
 | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the stages of a typical V-AC unit.
 |  | Definition 
 
        | -Double inlet dampers (2 for secondary containment). -Roll-o-matic filters.
 -Cooling coil.
 -Face and bypass dampers.
 -Heating coil.
 -Temperature element.
 -Fan.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the purpose of the HVAC syste.
 |  | Definition 
 
        | -Control environmental conditions for equipment and personnel. -Controlled flow and release.
 -Flow path is always low areas to higher radioactive areas.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the main supply fans.
 |  | Definition 
 
        | -Known as the 10 fans (V-AC-10A/B). -Normally both run.
 -Have cooling coil trip.
 -Trip on loss of Rx building exhaust fans (V-EF-24A/B).
 -Supply lower areas in the Rx building.
 -Powered by MCC-111/141.
 -Exhaust into plenum.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the concern with a loss of the main supply fans.
 |  | Definition 
 
        | High steam chase temperature causing a Group I isolation. |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the Rx building exhaust fans.
 |  | Definition 
 
        | -Know as the 24 fans (V-EF-24A/B). -Normally 1 fan runs.
 -Powered by MCC-111.
 -RWCU discharges into suction of 24 fans.
 -Exhaust into plenum.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe normal pressure in Rx building.
 |  | Definition 
 
        | -Negative 0.25" H2O as compaired to atmosphere. |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the normal pressure in the exhaust plenum.
 |  | Definition 
 
        | -Maintained at negative 0.5" H2O compaired to outside air. |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the plenum exhaust fans.
 |  | Definition 
 
        | -(V-EF-20/21/22). -Powered by MCC-132/132/122.
 -Exhaust fans to Rx building vent stack.
 -Fans are modulated to maintain exhaust plenum pressure.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the exhaust plenum rad monitor setpoint.
 |  | Definition 
 
        | 26mrem/hr or downscale of .1mrem/hr. |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the refuel floor fans.
 |  | Definition 
 
        | -Known as the 4 fans (V-AH-4A/B) -Powered by MCC-132/122).
 -Normally only 1 fan running.
 -Trips on loss of refuel exhaust fan (V-EF-28).
 -Safety related dampers fail closed on loss of air.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the refuel floor rad monitor setpoint.
 |  | Definition 
 
        | 50mrem/hr or downscale of .1mrem/hr. |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the refuel floor exhaust fan.
 |  | Definition 
 
        | -Known as the 28 fan (V-EF-28). -Powered by MCC-132.
 -If running and 4 fan is in auto, when flow is sensed the 4 fan will start.
 -If lost the 4 fan will trip.
 -Exhaust into plenum.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the sample station exhaust fan.
 |  | Definition 
 
        | -(V-EF-10). -Powered by MCC-132.
 -Exhausts into plenum.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the rad waste vent line.
 |  | Definition 
 
        | -Rad waste exhaust fans. -Has 2 fans in rad waste (V-FU-1/2).
 -Powered by MCC-111/141.
 -Has heating coil trip.
 -Discharges into plenum.
 -Maintains rad waste at -0.25" H20.
 -Interlocked with rad waste supply fans (V-MZ-3A/B).
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the cross-connect between 28 fan inlet and SBGT.
 |  | Definition 
 
        | -Damper opens (V-D-42) pens to connect duct on V-EF-24/28 together for SBGT operations. |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the HPCI room alarms.
 |  | Definition 
 
        | High temp: 97F. Low temp: 65F.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe Rx building temp alarm.
 |  | Definition 
 | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the ECCS room temp alarms and cooling supply.
 |  | Definition 
 
        | -100F. -SW is normal supply with ESW as b/u.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the RCIC room temp alarm.
 |  | Definition 
 | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the CRD pump room temp alarm and control.
 |  | Definition 
 
        | -Alarms at 104F. -Sw starts at 85F, second starts at 90F.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe recirc MG set room fans.
 |  | Definition 
 
        | -(V-SF-3/4). -Powered by MCC-133/122.
 -Modulate to keep room at .25" H2O positive pressure.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the sludge tank vent filter unit.
 |  | Definition 
 
        | -Vent for RW tanks: -Condensate phase, clean-up phase, spent resin, waste sludge.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the SJAE fan.
 |  | Definition 
 
        | -Known as the 26 fan (V-EF-26). -Suctions from SJAE room exhaust to plenum and dilution air for SBGT.
 -Normally runs.
 -Powered by MCC-132.
 -On SBGT initiation damper to SBGT isolates and directs to plenum.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the cond/demin MVP room fan.
 |  | Definition 
 
        | -Known as the 11 fan (V-EF-11). -Powered by MCC-132.
 -Normally runs.
 -Suctions from cond/demin MVP room and exhausts to plenum or SBGT dilution air.
 -SBGT initiation damper isolates to SBGT and aligns to plenum.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the turbine building fans.
 |  | Definition 
 
        | -(V-AH-1/2). -Neither fan normally ran.
 -Powered by MCC-121/142B.
 -Both start when ceiling temp reaches 250F.
 -At -0.2"H2O in plenum the fans trip and plenum room ceiling dampers shut.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the EDG fans.
 |  | Definition 
 
        | -(V-SF-9/10). -Powered by 12EDG/11EDG.
 -Start when EDG start signal or when bus is energized.
 -EDG building suction dampers open then discharge shut and vice versa.
 |  | 
        |  | 
        
        | Term 
 
        | HVAC 
 Describe the recombiner building exhaust fans.
 |  | Definition 
 
        | -(C-1004A/B). -Located in MVP room.
 -Discharge to plenum.
 -Fans trip on exhaust plenum press of -0.2"H2O.
 |  | 
        |  |