Term
FH

Describe the refuel platform rod block interlocks.
Definition
-If mode switch is in refuel and the refuel platform is not over the vessel then rod withdrawal is permitted.
-If mode switch in refuel and platform is over the vessel and:
-Grapple not full up, or
-Grapple loaded, or
-Frame mounted hoist loaded, or
-Monorail mounted hoist loaded, then
-Get a rod block.
Term
FH

Describe the refuel platform hoist power interlocks.
Definition
-Grapple hoist power is blocked if the refuel platform is over the vessel and all rods are not fully inserted.
-Frame mounted hoist power is blocked if the refuel platform is over the vessel and all rods are not fully inserted and the hoist is loaded.
-Monorail mounted hoist power is blocked if the refuel platform is over the vessel and all rods are not fully inserted and the hoist is loaded.
Term
FH

Describe the refuel platform drive power interlocks.
Definition
-Reverse power to the refuel platform is blocked if the mode switch is in STARTUP and the bridge approaches the core.
-Reverse power to refuel platform is blocked if all rods are not inserted and bridge approaches the core and grapple loaded, or grapple not full up, or monorail mounted hoist loaded, or frame mounted hoist loaded.
-Forward power to platform is never blocked.
Term
FH

Describe the service platform interlocks.
Definition
-If the jib crane hoist is loaded then get a rod block.
-If all rods are not inserted then power to the jib crane is blocked.
Term
FH

Describe the refuel interlocks - startup mode.
Definition
-If refuel platform is over the vessel and mode switch in s/u then get a rod block.
-If mode switch in s/u and refuel platform approaching the vessel then power to refuel bridge is blocked.