| Term 
 
        | 13KV Site Services Purpose |  | Definition 
 
        | Provides a reliable and backed up source f power to the 13KV Auxiliary Loop Electrical System |  | 
        |  | 
        
        | Term 
 
        | 13 KV Site Services    Design Basis |  | Definition 
 
        | 2 Redundant power sources suppling 480/240/120 to: Salem TSC/B Building/4KV Breaker Shop/Admin Building/Services Building/NOSF/Fab Shop/ Secondary Chemistry Lab/ TP&L Loads |  | 
        |  | 
        
        | Term 
 
        | What Bus Group Feeds Switching/Subststions 2,4,5 |  | Definition 
 | 
        |  | 
        
        | Term 
 
        | Which Substation/Switching Stations have Key interlocks and Why? |  | Definition 
 
        | 1 and 5 due to Line of sight seperation between the Switching station and the Substation.   6 is the newest style and has a built in Key interlock to ensure disconnects are not opened under load. |  | 
        |  | 
        
        | Term 
 
        | Which Substations have forced air cooling for their transformers? strip Heaters? How are they powered? |  | Definition 
 
        | 1,3,5 have cooling fans all have strip heaters. Both Fans and strip heaters are powered from 13KV to 120 VAC transformers |  | 
        |  | 
        
        | Term 
 
        | automatic recloser function and operation |  | Definition 
 
        | Fast acting circuit breaker that is designed to close again to clear non-persistant faults on overhead lines o buses. Our reclosures have been set up to be a "one shot to lockout". Meaning they will open upon fault and not reclose without manual manipulation |  | 
        |  | 
        
        | Term 
 
        | Which two recloser units are set up to open automatically on a loss of supply power? |  | Definition 
 
        | Reclosers 1 and 2 will open automatically upon a loss of supply power after a 20 sec time delay |  | 
        |  | 
        
        | Term 
 
        | Which Relosers will change their min trip settings when power loss is sensed? |  | Definition 
 
        | Reclosers 3/4/5 Settings will reduce from 480a to 240a |  | 
        |  | 
        
        | Term 
 
        | What power do the reclosers use to close? to open? |  | Definition 
 
        | AC Power is used to close the reclosers from being energized by either side of the recloser   Opening or "Trip" voltage is supplied by a self charged internal DC battery. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | U1 and U2 Plant computer Secondary Chem Lab Admin Telephone(DID) Cross Flow enclosure U1 Hydrogen Dryer |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | Maintenance Facilities- Building 470 Maintenance TP&L loads |  | 
        |  | 
        
        | Term 
 | Definition 
 | 
        |  | 
        
        | Term 
 | Definition 
 
        | Reverse Osmosis - Demin Plant SWIS Weld recept. |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | "B" Building/TSC U1/U2 Containment Maint. Power |  | 
        |  | 
        
        | Term 
 | Definition 
 
        | New Maintenance Shop Security Vehicle Barrier System |  | 
        |  |